RFScada Model 16ADI-9D2AO Specifications
Due to
continual improvements all published specifications are subject to change. SS1
option shown, SS1, V1, V2, V5, U1, U2, U5 radio specifications differ.
|
AC Operating voltage |
85 - 140 VAC 48 – 62 Hz
(85 – 264 VAC 48 – 62Hz if protective MOV changed) |
|
AC Power supply
certification |
UL, CE, CISPR/FCC Class
B |
|
DC Input Operating
voltage (note 2) |
10 to 28 Volts DC
|
|
DC Output Power (note 3) |
14.4 Volts DC 1 Amp
|
|
AC Power consumption |
<0.5 Amp |
|
DC Power consumption (at
12VDC) |
0.07 Amp no active relays
or 4-20mA; 0.28 Amp with all relays & 4-20mA active |
|
On board AC input fuse
rating |
2 Amp 115 VAC |
|
AC Input transient
protection |
Yes, 10,000A 120 Joule
150 V MOV on board |
|
DC Input transient
protection |
Yes, electronic fuse and
1500W MOV on board |
|
Enclosure rating |
UL 508, CSA and NEMA
1,2,3,4,4X,12, 13 IEC 529, IP66 |
|
Enclosure type
|
Fiberglass with stainless
steel hardware |
|
Enclosure door closure
types |
Lockable snap latch or
screw close available |
|
Dimensions |
11.75 H x 11.75 W x 6.75
D inches |
|
Weight |
8 Pounds |
|
Storage temperature
rating |
-40°C
to +85 °C |
|
Operating temperature
rating |
-10°C
to +75 °C (0 to 40 °C
for AC powered version) |
|
Humidity |
15-95% non-condensing |
|
Minimum telemetry update
rate |
5 times per second
standard ISM (bi-directional) |
|
Transmission method
|
Bi-directional, mode and
modulation type depend on model |
|
Operating frequency
|
148-174MHz VHF band,
450-490 MHz UHF band, 902-928 MHz ISM band |
|
RF data encryption method |
Proprietary 16 bit cyclic
redundancy checking with 50 channel hopping |
|
Signal data encryption
method |
Proprietary rolling code
plus 16 bit cyclic redundancy check |
|
Internal antenna supplied |
Yes, 2.1 dB Gain
omni-directional half wave dipole (ISM) |
|
Range with internal
antenna |
Up to 20 miles line of
sight depending on radio option. |
|
Range with external
antenna |
Up to 75 miles depending
on radio option. |
|
License required (USA) |
Not for SS, SS1 versions,
yes for V1, V2, V5, U1, U2 and U5 versions |
|
FCC approved |
Yes |
|
Network status
transmitted |
Yes |
|
Units in a network |
1 to 32 (255 under PC
control) |
|
Repeater Mode |
Standard |
|
Maximum number of inputs
in a network |
504, 252 digital & 252
analog (4032, 2016 digital & 2016 analog under PC control) |
|
Maximum number of outputs
in a network |
500, 252 digital & 248
analog (4000, 2016 digital & 1984 analog under PC control) |
|
Output signal source |
Any output may be driven
by any input, user programmable |
|
Digital Input signal
channels transmitted (per unit) |
8 plus communication
state |
|
Digital Input channel
signal type |
Low voltage (5V) contacts
or logic level |
|
Digital Input signal
voltage required |
None |
|
Digital Input signal
transient protection |
Yes, 600W TVS surge and
RF filters |
|
Digital Input signal
status indication |
Yes, on board LED’s, one
per channel. |
|
Digital Input signal
cable length |
Maximum 250 feet
recommended |
|
Digital Input signal
de-bounce time |
Approximately 0.25 second |
|
Analog Input channels
transmitted (per unit) |
8 plus temperature, DC
Voltage and radio signal strength (SS1 version) |
|
Analog Input signal type
|
4-20 mA grounded, 0-5
Volt DC, 0-10 Volt DC, Digital jumper selectable. |
|
Analog Input transducer
on board power supply |
On board 15 VDC with AC
power or ~1 Volt below DC supply Voltage. |
|
Transducer on board power
supply protection |
Yes, current limited with
electronic fuse |
|
Analog Input transducer
power source |
May be external or use on
board supply |
|
Analog Input transient
protection |
Yes, 600W TVS surge and
RF filters |
|
Analog Input signal cable
length |
Max. 250 feet recommended |
|
Analog Input signal
accuracy |
0.024% (12 bit analog to
digital conversion) |
|
Digital output (received)
signal channels |
8 |
|
Digital output (received)
status channels |
1 for system status |
|
Digital output (received)
relay contact ratings |
SPDT 10 Amp at 115 VAC, 5
Amp at 30 VDC |
|
Digital output (received)
signal indication |
Yes, 8 on board LED’s,
one per channel, show relay states |
|
Digital output (received)
system status indication |
Yes, on board LED shows
system status |
|
Analog 4-20 mA outputs
capability |
2 Standard |
|
Modbus capability |
Built in, every unit is a
Modbus RTU slave |
|
Modbus interface built in |
Yes, both RS-232 and 2
wire RS-485 on board automatic selection |
|
Inputs that may be
monitored by Modbus |
Every analog input,
digital input, temperature and DC voltage |
|
Outputs that may be
controlled by Modbus |
Every analog output and
digital output |
|
Time to default outputs
after signal loss |
User adjustable, 20
seconds to over 7 days |
|
Additional status LED’s |
7, two each for data
transmission/ reception plus one for Modbus / system activity |
Notes:
- Generic radio parameters refer to the ISM version.
- The unit may be powered from either AC source or DC
source, or a combination of both.
- This DC output is available for external 4-20mA
transducers and an external radio.
RFScada Model 8ADI-9DO Specifications
Due to continual improvements all published
specifications are subject to change. These refer to the SS version; VHF and
UHF radio specifications differ.
|
AC
Operating voltage (note 1) |
115
VAC +/- 10% 48 – 62Hz |
|
DC
Operating voltage (note 1) |
10
to 28 Volts DC |
|
AC
Power consumption |
<0.5
Amp |
|
DC
Power consumption |
<0.1
Amp no active relays or 4-20mA; 0.7 Amp with all relays & 4-20mA active |
|
On
board AC input fuse rating |
2
Amp 115 VAC |
|
AC
Input transient protection |
Yes,
10,000A 120 Joule 150V MOV on board |
|
DC
Input transient protection |
Yes,
electronic fuse and 1500W MOV on board |
|
Enclosure rating |
UL
508, CSA and NEMA 1,2,3,4,4X,12, 13 IEC 529, IP66 |
|
Enclosure type |
Fiberglass with stainless steel hardware |
|
Enclosure door closure types |
Lockable snap latch or screw close available |
|
Dimensions |
11.75 H x 11.75 W x 6.75 D inches |
|
Weight |
8
Pounds |
|
Storage temperature rating |
-40°C
to +85 °C |
|
Operating temperature rating |
-30°C
to +75 °C |
|
Humidity |
15-95% non-condensing |
|
Minimum telemetry update rate |
5
times per second (bi-directional) |
|
Transmission method |
Bi-directional, mode and modulation type depend on model |
|
Operating frequency ranges |
146-174MHz VHF band, 450-490 MHz UHF band, 902-928 MHz ISM band |
|
RF
data encryption method |
Proprietary 16 bit cyclic redundancy checking with 25 channel hopping |
|
Signal data encryption method |
Proprietary rolling code plus 16 bit cyclic redundancy check |
|
Internal antenna supplied |
Yes,
2.1 dB Gain omni-directional half wave dipole (ISM) |
|
Range with internal antenna |
Up
to 5-7 miles line of sight. |
|
Range with external antenna |
Up
to 25 miles line of sight. |
|
License required |
None
(USA) |
|
FCC
approved |
Yes |
|
Network status transmitted |
Yes |
|
Units in a network |
1 to
32 |
|
Maximum number of inputs in a network |
512,
256 digital and 256 analog |
|
Maximum number of outputs in a network |
512,
256 digital and 256 analog |
|
Output signal source |
Any
output may be driven by any input, user programmable |
|
Digital Input signal channels transmitted (per unit) |
8
plus communication state |
|
Digital Input channel signal type |
Low
voltage (5V) contacts or logic level |
|
Digital Input signal voltage required |
None |
|
Digital Input signal transient protection |
Yes,
600W TVS surge and RF filters |
|
Digital Input signal status indication |
Yes,
on board LED’s, one per channel. |
|
Digital Input signal cable length |
Maximum 250 feet recommended |
|
Digital Input signal de-bounce time |
Approximately 0.25 second |
|
Analog Input channels transmitted (per unit) |
8 |
|
Analog Input signal type |
4-20
mA grounded or 0-10 VDC (factory configured) |
|
Analog Input transducer on board power supply |
On
board ~18 VDC with 115VAC or ~1 Volt below DC supply Voltage.
|
|
Transducer on board power supply protection |
Yes,
current limited with electronic fuse |
|
Analog Input transducer power source |
May
be external or use on board supply |
|
Analog Input transient protection |
Yes |
|
Analog Input signal cable length |
Max.
250 feet recommended |
|
Analog Input signal accuracy |
0.5%
(10 bit analog to digital conversion) |
|
Digital output (received) signal channels |
8 |
|
Digital output (received) status channels |
1
for system status |
|
Digital output (received) relay contact ratings |
SPDT
10 Amp at 115 VAC, 5 Amp at 30 VDC |
|
Digital output (received) signal indication |
Yes,
8 on board LED’s, one per channel, show relay states |
|
Digital output (received) system status indication |
Yes,
on board LED shows system status |
|
Analog 4-20 mA outputs, standard unit |
0 |
|
Analog 4-20 mA outputs, with option AO2 |
2 |
|
Analog 4-20 mA outputs, with option AO4 |
4 |
|
Analog 4-20 mA outputs, with option AO8 |
8 |
|
Analog out type |
4-20
mA non isolated |
|
Analog output power source |
On
board. |
|
Modbus capability |
Built in, every unit is a Modbus RTU slave |
|
Modbus interface built in |
Yes,
both RS-232 and 2 wire RS-485 on board, jumper selectable
|
|
Inputs that may be monitored by Modbus |
Every analog input, digital input and unit DC voltage on the network |
|
Outputs that may be controlled by Modbus |
Every analog output and digital output |
|
Time
to default outputs after system fail |
User
adjustable, default is 10 seconds |
|
Additional status LED’s |
3,
one each for data transmission, reception and Modbus activity |
Notes:
The unit may be powered from either a 115 VAC source or an
external DC source, or a combination of both to allow fully functional and
continuous operation in the event of either external power source failing
RFScada Model 4ADI-5DO2
Specifications
Due to continual improvements all published
specifications are subject to change. SS1 option shown, SS1, V1, V2, V5, U1,
U2, U5 radio specifications differ.
|
AC Operating voltage |
85 - 140 VAC 48 – 62
Hz (85 – 264 VAC 48 – 62Hz if protective MOV changed) |
|
AC Power supply
certification |
UL, CE, CISPR/FCC Class
B |
|
DC Input Operating
voltage (note 2) |
10 to 28 Volts DC
|
|
DC Output Power (note
3) |
14.4 Volts DC 1 Amp
|
|
AC Power consumption |
<0.5 Amp |
|
DC Power consumption
(at 12VDC) |
0.07 Amp no active
relays or 4-20mA; 0.20 Amp with all relays & 4-20mA active |
|
On board AC input fuse
rating |
2 Amp 115 VAC |
|
AC Input transient
protection |
Yes, 10,000A 120 Joule
150 V MOV on board |
|
DC Input transient
protection |
Yes, electronic fuse
and 1500W MOV on board |
|
Enclosure rating |
UL 508, CSA and NEMA
1,2,3,4,4X,12, 13 IEC 529, IP66 |
|
Enclosure type
|
Fiberglass with
stainless steel hardware |
|
Enclosure door closure
types |
Lockable snap latch or
screw close available |
|
Dimensions |
11.75 H x 11.75 W x
6.75 D inches |
|
Weight |
8 Pounds |
|
Storage temperature
rating |
-40°C
to +85 °C |
|
Operating temperature
rating |
-10°C
to +75 °C (0 to 40 °C
for AC powered version) |
|
Humidity |
15-95% non-condensing |
|
Minimum telemetry
update rate |
5 times per second
standard ISM (bi-directional) |
|
Transmission method
|
Bi-directional, mode
and modulation type depend on model |
|
Operating frequency
|
148-174MHz VHF band,
450-490 MHz UHF band, 902-928 MHz ISM band |
|
RF data encryption
method |
Proprietary 16 bit
cyclic redundancy checking with 50 channel hopping |
|
Signal data encryption
method |
Proprietary rolling
code plus 16 bit cyclic redundancy check |
|
Internal antenna
supplied |
Yes, 2.1 dB Gain
omni-directional half wave dipole (ISM) |
|
Range with internal
antenna |
Up to 20 miles line of
sight depending on radio option. |
|
Range with external
antenna |
Up to 75 miles
depending on radio option. |
|
License required (USA) |
Not for SS1 versions,
yes for V1, V2, V5, U1, U2 and U5 versions |
|
FCC approved |
Yes |
|
Network status
transmitted |
Yes |
|
Units in a network |
1 to 32 (255 under PC
control) |
|
Repeater Mode |
Standard |
|
Maximum number of
inputs in a network |
504, 252 digital & 252
analog (4032, 2016 digital & 2016 analog under PC control) |
|
Maximum number of
outputs in a network |
500, 252 digital & 248
analog (4000, 2016 digital & 1984 analog under PC control) |
|
Output signal source |
Any output may be
driven by any input, user programmable |
|
Digital Input signal
channels transmitted (per unit) |
4 to 8 plus
communication state |
|
Digital Input channel
signal type |
Low voltage (5V)
contacts or logic level |
|
Digital Input signal
voltage required |
None |
|
Digital Input signal
transient protection |
Yes, 600W TVS surge and
RF filters |
|
Digital Input signal
status indication |
Yes, on board LED’s,
one per channel. |
|
Digital Input signal
cable length |
Maximum 250 feet
recommended |
|
Digital Input signal
de-bounce time |
Approximately 0.25
second |
|
Analog Input channels
transmitted (per unit) |
4 plus temperature, DC
Voltage and radio signal strength (SS1 version) |
|
Analog Input signal
type |
4-20 mA grounded, 0-5
Volt DC, 0-10 Volt DC jumper selectable. |
|
Analog Input transducer
on board power supply |
On board 15 VDC with AC
power or ~1 Volt below DC supply Voltage. |
|
Transducer on board
power supply protection |
Yes, current limited
with electronic fuse |
|
Analog Input transducer
power source |
May be external or use
on board supply |
|
Analog Input transient
protection |
Yes, 600W TVS surge and
RF filters |
|
Analog Input signal
cable length |
Max. 250 feet
recommended |
|
Analog Input signal
accuracy |
0.5% (12 bit analog to
digital conversion) |
|
Digital output
(received) signal channels |
4 |
|
Digital output
(received) status channels |
1 for system status |
|
Digital output
(received) relay contact ratings |
SPDT 10 Amp at 115 VAC,
5 Amp at 30 VDC |
|
Digital output
(received) signal indication |
Yes, 4 on board LED’s,
one per channel, show relay states |
|
Digital output
(received) system status indication |
Yes, on board LED shows
system status |
|
Analog 4-20 mA outputs
capability |
None |
|
Modbus capability |
Built in, every unit is
a Modbus RTU slave |
|
Modbus interface built
in |
Yes, both RS-232 and 2
wire RS-485 on board, jumper selectable |
|
Inputs that may be
monitored by Modbus |
Every analog input,
digital input, temperature and DC voltage |
|
Outputs that may be
controlled by Modbus |
Every analog output and
digital output |
|
Time to default outputs
after signal loss |
User adjustable, 20
seconds to over 7 days |
|
Additional status LED’s |
5, two each for data
transmission/ reception plus one for Modbus / system activity |
Notes:
1.
Generic radio parameters refer to the ISM version.
2.
The unit may be powered from either AC source or DC source, or a
combination of both to allow fully functional and continuous operation in the
event of either external power source failing.
3.
This DC output is available for external 4-20mA transducers and an
external radio.
RFScada Model 4ADI-5DO
Specifications
Due to continual improvements
all published specifications are subject to change. SS option shown, SS1, V1,
V2, V5, U1, U2, U5 radio specifications differ.
|
AC
Operating voltage (note 1) |
85 -
140 VAC 48 – 62 Hz (85 – 264 VAC 48 – 62Hz if protective MOV changed) |
|
AC
Power supply certification (note 1) |
UL,
CE, CISPR/FCC Class B |
|
DC
Input Operating voltage (note 2) |
10
to 28 Volts DC |
|
DC
Output Power (note 3) |
15
Volts DC 1 Amp |
|
AC
Power consumption |
<0.5
Amp |
|
DC
Power consumption (at 12VDC) |
0.07
Amp no active relays or 4-20mA; 0.28 Amp with all relays & 4-20mA active |
|
On
board AC input fuse rating |
2
Amp 115 VAC |
|
AC
Input transient protection |
Yes,
10,000A 120 Joule 150 V MOV on board |
|
DC
Input transient protection |
Yes,
electronic fuse and 1500W MOV on board |
|
Enclosure rating |
UL
508, CSA and NEMA 1,2,3,4,4X,12, 13 IEC 529, IP66 |
|
Enclosure type |
Fiberglass with stainless steel hardware |
|
Enclosure door closure types |
Lockable snap latch or screw close available |
|
Dimensions |
11.75 H x 11.75 W x 6.75 D inches |
|
Weight |
8
Pounds |
|
Storage temperature rating |
-40°C
to +85 °C |
|
Operating temperature rating |
-30°C
to +75 °C (0 to 40
°C
for AC powered version) |
|
Humidity |
15-95% non-condensing |
|
Minimum telemetry update rate |
5
times per second standard (bi-directional) |
|
Transmission method |
Bi-directional, mode and modulation type depend on model |
|
Operating frequency |
148-174MHz VHF band, 450-490 MHz UHF band, 902-928 MHz ISM band |
|
RF
data encryption method |
Proprietary 16 bit cyclic redundancy checking with 25 channel hopping |
|
Signal data encryption method |
Proprietary rolling code plus 16 bit cyclic redundancy check |
|
Internal antenna supplied |
Yes,
2.1 dB Gain omni-directional half wave dipole (ISM) |
|
Range with internal antenna |
Up
to 14 miles line of sight depending on radio option. |
|
Range with external antenna |
Up
to 75 miles depending on radio option. |
|
License required (USA) |
Not
for SS, SS1 versions, yes for V1, V2, V5, U1, U2 and U5 versions |
|
FCC
approved |
Yes
|
|
Network status transmitted |
Yes |
|
Units in a network |
1 to
32 |
|
Maximum number of inputs in a network |
504,
252 digital and 252 analog |
|
Maximum number of outputs in a network |
500,
252 digital and 248 analog |
|
Output signal source |
Any
output may be driven by any input, user programmable |
|
Digital Input signal channels transmitted (per unit) |
4
plus communication state |
|
Digital Input channel signal type |
Low
voltage (5V) contacts or logic level |
|
Digital Input signal voltage required |
None |
|
Digital Input signal transient protection |
Yes,
600W TVS surge and RF filters |
|
Digital Input signal status indication |
Yes,
on board LED’s, one per channel. |
|
Digital Input signal cable length |
Maximum 250 feet recommended |
|
Digital Input signal de-bounce time |
Approximately 0.25 second |
|
Analog Input channels transmitted (per unit) |
4
plus temperature, DC Voltage and radio signal strength (SS1 version) |
|
Analog Input signal type |
4-20
mA grounded, 0-5 Volt DC, 0-10 Volt DC jumper selectable. |
|
Analog Input transducer on board power supply |
On
board 15 VDC with AC power or ~1 Volt below DC supply Voltage.
|
|
Transducer on board power supply protection |
Yes,
current limited with electronic fuse |
|
Analog Input transducer power source |
May
be external or use on board supply |
|
Analog Input transient protection |
Yes,
600W TVS surge and RF filters |
|
Analog Input signal cable length |
Max.
250 feet recommended |
|
Analog Input signal accuracy |
0.5%
(10 bit analog to digital conversion) |
|
Digital output (received) signal channels |
4 |
|
Digital output (received) status channels |
1
for system status |
|
Digital output (received) relay contact ratings |
SPDT
10 Amp at 115 VAC, 5 Amp at 30 VDC |
|
Digital output (received) signal indication |
Yes,
4 on board LED’s, one per channel, show relay states |
|
Digital output (received) system status indication |
Yes,
on board LED shows system status |
|
Analog 4-20 mA outputs capability |
None |
|
Modbus capability |
Built in, every unit is a Modbus RTU slave |
|
Modbus interface built in |
Yes,
both RS-232 and 2 wire RS-485 on board, jumper selectable
|
|
Inputs that may be monitored by Modbus |
Every analog input, digital input, temperature and DC voltage |
|
Outputs that may be controlled by Modbus |
Every analog output and digital output |
|
Time
to default outputs after system fail |
User
adjustable, default is 10 seconds |
|
Additional status LED’s |
5,
two each for data transmission/ reception plus one for Modbus / system
activity |
Notes:
1.
The AC power supply is a factory installed option.
2.
The unit may be powered from either AC source or DC source, or a
combination of both to allow fully functional and continuous operation in the
event of either external power source failing.
3.
This DC output is available with AC power option for external 4-20mA
transducers or an external radio.
RFScada Model 2DI-4DO Specifications
Due to continual improvements all published specifications are
subject to change
|
AC Operating voltage (note 1) |
115 VAC +/- 10% 48 – 62Hz |
|
DC Operating voltage (note 1) |
10 to 18 Volts DC |
|
AC Power consumption |
<0.5 Amp |
|
DC Power consumption |
< 0.25 Amp |
|
On board AC input fuse rating |
2 Amp 115 VAC |
|
AC Input transient protection |
Yes, 10,000A 120 Joule MOV on board |
|
Enclosure rating |
UL 508, CSA and NEMA 1,2,3,4,4X,12, 13 IEC 529, IP66 |
|
Enclosure type |
Fiberglass with stainless steel hardware |
|
Enclosure door closure types |
Lockable snap latch or screw close available |
|
Dimensions |
11.75 H x 11.75 W x 6.75 D inches |
|
Weight |
8.5 Pounds |
|
Temperature rating (note 2) |
-20°C
to +70 °C |
|
Humidity |
15-95% non-condensing |
|
Minimum telemetry update rate |
4 times per second (bi-directional) |
|
Transmission method |
Bi-directional spread spectrum frequency hopping |
|
Operating frequency |
902-928 MHz ISM band |
|
RF data encryption method |
Proprietary 16 bit cyclic redundancy checking with 25 channel
hopping |
|
Signal data encryption method |
Proprietary rolling code plus 16 bit cyclic redundancy check |
|
Internal antenna supplied |
Yes, 2.1 dB Gain omni-directional half wave dipole |
|
Range with internal antenna |
| |